MACHINE CONNECTIVITY · INJECTION MOULDING
Digitalising existing injection moulding machines and using production data
Sensors, interfaces and production data to make effective use of existing equipment.
Many plastics-processing plants operate injection moulding machines from different manufacturers and generations. Some have modern industrial interfaces; others provide basic electrical signals and internal records with limited access. This diversity determines what can be measured, how it is interpreted and the cost of integrating the equipment.
A modular digitalisation strategy assesses existing assets and selects the signals needed to address a production problem. The first step is to identify the decisions that require better information.
Start with the plant’s questions
A plant seeking to understand capacity losses needs to know its productive periods, stops and cycles. Energy analysis requires measuring power, integrating it over defined intervals to determine energy, and associating these measurements with production and auxiliary equipment. Investigating part stability is likely to require process variables, batch traceability and quality results.
Before selecting sensors, define the indicator, the associated physical phenomenon, the required time resolution, the sources of context and the person responsible for acting on the information.
Which signals to acquire from the injection moulding machine
Depending on its generation and controller, a machine may provide states, alarms, cycles, recipe variables, actual process values and data through communication interfaces. Some machines offer OPC UA or other interfaces, while others require adaptation of the available signals.
A validated signal and a robust event acquisition system may be sufficient to record running status or cycles. For pressure, temperature or motion profiles, sampling frequency, accuracy and synchronisation become more important. The variable and its measurement location determine the conclusions that can be drawn.
For plastics machinery, OPC 40077 defines a data model for exchange between injection moulding machines and manufacturing execution systems. Its use depends on compatible controller support. See our guide to OPC UA, MQTT and EUROMAP.
Include auxiliary equipment when the problem requires it
Cell productivity and consumption also depend on cooling, drying, material feeding, robotics, conveying and other auxiliaries. An interruption in auxiliary equipment can affect production even when the injection moulding machine remains operational.
In an energy analysis, measuring a single circuit can obscure the relative contribution of auxiliary equipment. Separating selected electrical supplies allows consumption to be examined during production, waiting periods, preheating and product changeovers.
This application relates to KERN IoP | ENERGY: Cell. Designing the measurement system requires a review of electrical diagrams, installation conditions and appropriate safety practices.
Turn signals into comparable records
The same cycle time can represent different conditions when the mould, number of active cavities, material or quality changes. To interpret records correctly, retain the product reference, production order, tooling and process conditions.
Energy indicators require equivalent normalisation. kWh/cycle, kWh/kg or cost per batch can be useful when the included equipment, output quantity, measurement period and proportion of conforming parts have been established.
Integration, cybersecurity and maintenance
The machine must continue to operate within the limits defined by its manufacturer and the plant’s risk assessment. Read and write access must be managed separately, industrial networks segmented where appropriate, credentials managed and connection points documented.
The IEC 62443 series provides guidance for industrial cybersecurity. For legacy assets, available support, network architecture and compensating measures determine the risk associated with connectivity.
Maintaining the solution includes calibration where applicable, configuration backups, timestamp integrity, software updates and version control. A pilot verifies these conditions before coverage is expanded.
A practical implementation sequence
- Select a recurring problem and estimate its impact using available data.
- Audit interfaces, signals, auxiliary equipment, electrical diagrams and safety constraints.
- Define a minimum dataset and a reference condition.
- Implement data acquisition and contextualisation on one machine or cell.
- Check the records against operator observations, production data and quality results.
- Implement an improvement and verify its results.
- Document the architecture and the conditions for scaling up.
López Almendros and Aguilar Pérez (2025) describe modular applications in four plastics-processing SMEs. Comparing their results requires retaining the context of each intervention.
PM Tec Engineering, through its Industry 4.0 division, KERN IoP, develops signal acquisition with SMARTHUB, MONITOR monitoring and industrial engineering services. The scope is defined after reviewing the characteristics of each machine and process.
Further reading: digitalisation in plastics-processing SMEs and productivity and OEE.
References
- IEC. (2024). IEC 62443-2-1:2024. Security for industrial automation and control systems — Part 2-1. International Electrotechnical Commission.
- López Almendros, A., & Aguilar Pérez, T. (2025). Real-world validation of a modular digital architecture in plastic manufacturing SMEs. The International Journal of Advanced Manufacturing Technology, 141, 1905–1916. DOI.